Regulations on calculating air intake and exhaust volume when the generator room uses clean ventilation:
When the generator room uses air cooling, the air inlet volume is calculated based on waste removal. heat in the generator room.
When the generator room is cooled by water, the amount of ventilation required to remove harmful gases must be calculated and determined. The permitted amount of harmful gases is: CO is 30 mg/m3 and acrolein is 0.3 mg/m3, or the air intake volume is calculated based on equal size at 20 m3 (KWh).
3. The exhaust air volume is the intake air volume minus the combustion air volume.
General ventilation and process air supply in the diesel engine room are carried out by HVAC professionals. Others are determined by electrical major. To dore simple: when the diesel engine room is not producing electricity, the air supply and exhaust is provided by HVAC professionals and when the machines in the diesel engine room are working, the power supply process air is also provided at this time by the HVAC department; . As with process smoke extraction, these are determined by the electrical sector.