No. The generator's chimney dissipates heat, impacting the weak power lines inside.
It is preferable not to install a high current shaft next to the elevator shaft, but this is permitted without conditions. The main consideration is security issues. Once there is a fire in a high-current shaft, it will be harmful to the elevator (of course, the possibility is relatively small).
"Electrical Design Code for Civil Buildings" JGJ16-2008:
There should be no flues, heating pipes or other installations that dissipate large amounts of heat or humidity near electrical conduits (including current weak trees).
Electrical conduits should avoid being adjacent to elevator shafts and stairwells when conditions permit.
Relevant data on the design of the diesel generator rooml
Unit power (kW) Standard machine room (length, width and height in mm) Exhaust shaft and outlet area with fan (㎡) Air inlet area ㎡ (plus fan ) Air inlet area ㎡ (natural air inlet) Fan exhaust flow (m?/min) Unit size (length, width and height mm) Weight (kg) Area between air tanks fuel (㎡)
< p>220 7000×4000 ×4500 1.6 2.0 4.0 490 3000×980×1530 3100 2275 7200×4000×4500 1.7 2.1 4.2 490 3150×980×1530 3250 2
310 7200×400 0×4500 1.7 2.1 4.2 490 3150×980×1530 3400 3
< p>330 7300×4250×4500 2.3 3.0 6.0 490 3300×1250×1800 3600 < p>360 7300×4380×45 00 2.6 3.2 6.4 490 3300× 1380×1550 3700 3400 7550×4250×4500 2.6 3.2 6.4 588 3550×1250×1800 4350
4 40 7750 ×4250×4500 3, 0 3.5 7.0 588 3750×1250×1800 4800 4
500 7750×4920×4500 3.0 4.5 9.0 735 3750 × 1920 × 2300 5000 4
550 7750 × 4920 × 4500 3.2 4.5 9.0 735 3750 × 1920 × 2300 5400 4
660 8650 × 4650 × 5000 4. 0 6.0 12.0 900 4650×1630×2320 9250 4
704 8650×4650×5000 4.0 6.0 12.0 900 4650×1630×2320 9350 5
1. About the exhaust pipe well (mandatory) The minimum clearance size required by the manufacturer is: 800 x 800 mm for a generator; 1200 x 1200 mm for two generators; Increase appropriately when conditions permit.
2. Regarding the clearance size of the spray dusting room (suitable for installation): 1800 x 2000 mm when a generator is used; 1800 x 2800 mm when two generators are used together.