Floor requirements fordiesel generator roomand basement oil storage room:
1 The Diesel generator room shall consist of. in fire-resistant steel Separation walls below 2:00 and floor slabs below 1:50 separate it from the rest.
2. A separate oil storage room should be installed. The oil storage capacity should not exceed the required quantity for 8 hours. Measures should be taken to prevent leaks and oil leaks. ventilation pipe (exterior); the fuel oil storage room must use a firewall separate from the generator; When the door needs to be opened on the fire wall, a class A fire door that can close by itself must be installed.
3. Use independent fire protection partitions and separate fire protection zones.
The diesel generator room must comply withThe following regulations:
1. It must be located on the first floor or the first or second floor of the basement.
2. It should not be placed on the upper floor, lower floor or next to busy places.
3. Fire partitions with a fire resistance rating of at least 2.00 h and non-combustible floor slabs of 1.50 h must be used to separate them from other parts. Doors must use Class A fire doors.
4. When an oil storage room is installed in the engine room, its total storage capacity must not exceed 1 m3 and the oil storage room must be separated from the generator room by a fire partition. . with a fire resistance rating of at least 3.00 h; confirm. When it is necessary to open the door on the fire partition, a class A fire door must be installed.
5. Fire alarm devicesmust be installed.
6. Fire extinguishing installations suitable for the capacity of the diesel generator and the size of the building must be installed. When an automatic sprinkler system is installed in other parts of the building, an automatic sprinkler system. must be installed in the engine room.