The size of our 100 kW product is 2450 × 750 × 1500 (L × W × H mm). Regarding the required size of a room, this element must also take into account the issues of heat dissipation and air intake and exhaust. a meter and a half from the wall. It is best to place the front tank of the radiator at least 2 meters from the wall. It is best to make the intake and exhaust pipes separately. Install an intake and exhaust fan in the room. Also pay attention to the location of fuel tanks and the location of fire extinguishers, distribution boxes, spare parts, tools, etc. Calculated this way, a room larger than 30 square meters is preferable. If it's smaller, place other items in other rooms. Our customers also have a separate small room for the fuel tank.
Remember that if the room is too small, the dissipationthermal of the machine will be affected.
The generator installation shall be designed to meet all anticipated operation and maintenance requirements; the complete installation must comply with local government building regulations, fire regulations and other applicable regulations; aspect matters, it’s very important.
1. Make sure the generator is protected from rain, sun, wind, etc. in the engine room
2. is smooth and has sufficient ventilation area, while guiding the hot air exhausted from the radiator out of the computer room and preventing its backflow;
3. Ensure that exhaust gases generated when the unit is operating are exhausted from the computer room. the computer room, and minimize the impact on the environment; The muffler and exhaust pipe must be vented from the roof, and the support frame allowsu exhaust pipe from expanding. It is absolutely prohibited to install the exhaust system directly on the unit:
4. There should be sufficient space around the generator to facilitate cooling, operation and maintenance of the unit. Generally speaking, no other objects are allowed within a radius of 1 to 1.5 meters around and 1.5 to 2 meters above.
5 The computer room must be equipped with fire extinguishing equipment of the specified level;
6. The engine room shall be equipped with corresponding emergency lighting measures to facilitate operation and maintenance;
7. Do not store flammable and explosive objects in the engine room.