Analysis of Answer C: Design parameters of water spray fire extinguishing system: When used for fire extinguishing and fire fighting purposes, the pressure fire extinguishing operation of the water mist nozzle shall not be less than 0.35 MPa when used for protection purposes and; for cooling purposes it should not be less than 0.2 MPa. Because the diesel generator room of the high-rise public building is equipped with a water spray fire extinguishing system. Then the fire extinguishing working pressure of the water mist nozzle of the system should not be low.
What type of fire suppression system should be installed in the diesel generator room?
Introduction What type of fire suppression system should be installed in the diesel generator room? Answer C: Design parameters of water spray fire extinguishing system: When used for fire extinguishing and fire fighting purposes, the extinguishing working pressure d