Many customers do not pay much attention to some details of the assembly process after purchasing diesel generator sets. For example, the assembly environment is very dusty, which may cause friction damage after entering the unit equipment. is relatively humid, allowing moisture to penetrate easily. Enter inside the device. Regarding these neglected details, Tenglong Generator Set made a summary:
When assembling the generator set, please pay attention to:
1. The installation site should be well ventilated and the generator end must have sufficient air inlet and good air outlet at the end of the diesel engine. The air outlet area should be more than 1.5 times larger than the water tank area.
2. The area around the installation site must be kept clean and items likely to generate gases and vapors corrodesives such as acids and alkalis should be avoided nearby. Fire extinguishing devices should be equipped wherever possible.
3. When used indoors, the smoke exhaust pipe must be directed outside. The diameter of the pipe must be ≥ the diameter of the silencer smoke outlet pipe. The connected pipe should not have more. more than 3 bends to ensure that the exhaust pipe is To ensure smooth flow of smoke, the pipe should be tilted downward 5-10 degrees to avoid rainwater injection; If the exhaust pipe is installed vertically upwards, a rain cover must be installed.
4. When the foundation is concrete, flatness should be measured with a level ruler during installation to ensure the unit is secured on a level foundation. There must be special anti-vibration pads or anchor bolts into be the unity and the foundation.
5. The shell of the generator set must have reliable protective grounding. For generators that require a neutral point to be directly grounded, the neutral grounding should be done by professionals and equipped with lightning protection devices. It is prohibited to use commercial food. The electrical grounding device leads the neutral point to be directly grounded.
6. The two-way switch between generator and mains must be very reliable to prevent reverse power transmission. The reliability of the two-way switch wiring must be inspected and approved by the local power supply department.
Paying attention to the above details can effectively avoid unnecessary damage to the equipment before use, and subsequent use can also proceed normally, which plays a certain role.n preventive role in terms of damage and corrosion.
1. The installation site must be well ventilated, with sufficient air inlets on the generator side and good air outlets on the diesel engine side. The air outlet area should be more than 1.5 times larger than the water tank area.
2. The area around the installation site should be kept clean, and objects that may produce corrosive gases and vapors such as acids and alkalis should be avoided nearby. Fire extinguishing devices should be equipped wherever possible.
3. When used indoors, the smoke exhaust pipe must be connected outdoors. The diameter of the pipe must be greater than the diameter of the silencer smoke outlet pipe. the connected pipe should not exceed 3 to ensure that the exhaust pipe is To ensure smooth flow of smoke, the pipe should be inclined towardsthe bottom 5-10 degrees to avoid rainwater injection if the exhaust pipe is installed vertically upwards, a rain cover should be installed; installed.
4. When the foundation is concrete, flatness should be measured with a level ruler during installation to ensure the unit is secured to a level foundation. There must be special anti-vibration pads or anchor bolts between the unit and the foundation.
5. The unit shell must have reliable protective grounding, andFor generators whose neutral point is directly grounded, the neutral point must be professionally grounded and equipped with protective devices against lightning. It is strictly prohibited to use the mains grounding device to directly ground the neutral point.