The installation requirements of the diesel generator set mainly include:
If the diesel generator is used indoors, the exhaust pipe should be connected outdoors and the diameter of the pipe exhaust pipe must be greater than the diameter of the muffler exhaust pipe. There should be no more than 3 bends in the pipeline to ensure smooth flow of smoke exhaust, and the pipe should be inclined downward 5-10 degrees to avoid rainwater injection if the exhaust pipe is used; is installed vertically upwards, a rain cover must be installed.
If it is an indoor machine room, the installation location should be well ventilated. There should be sufficient air inlets on the generator side and good air outlets on the diesel engine side. the air outlet should be at least 1.5 times larger than the water tank area.
Avoid place near the diesel generator set, which can produce acidity and alkalinity. For articles containing corrosive gases and vapors, the engine room must be equipped with fire extinguishing devices.
When the foundation is concrete, a level ruler should be used to measure its level during installation so that the unit can be fixed on a level foundation. There must be special anti-vibration pads or foot bolts. between the unit and the foundation.
The two-way switch between the diesel generator set and the mains power supply must be very reliable to prevent reverse power transmission. The reliability of the two-way switch wiring must be inspected and approved by the local power supply department.
The unit shell must have reliable protective earthing. For generators that require a neutral point to be directlyearthed, it is strictly prohibited to use the mains earthing device to directly earth the neutral point. grounded by professionals. Ground and install lightning protection.
The choice of the installation location of the unit is generally based on easy operation, good ventilation, convenient electrical distribution connection, economical and conducive to the maintenance of the unit:
1) Ensure the machine room The inlet and exhaust of air is smooth.
2) Ensure that the noise and smoke generated by the device during operation pollute the environment as little as possible.
3) It should provide sufficient space around the diesel generator set space to facilitate cooling, operation and maintenance of the unit . Generally, there is a space of 1 to 1.5 meters around the unit (except silent units).uses).
4) Make sure the unit is protected from rain, exposure to sunlight (except for quiet units), overheating and frost damage.
5) Avoid storing flammable and explosive objects around the diesel generator.