Regulations on the location of the diesel generator room: The diesel generator room can be arranged on the first floor of a high-rise building or podium or in the basement, and must comply with the regulations following: A. The diesel generator room must use fire-resistant material with a fire resistance rating of at least 2.00h. The partition and the 1.50 h floor slab separate it from the other parts. B. An oil storage room shall be provided in the diesel generator room and its total storage capacity shall not exceed the required quantity for 8 hours. The oil storage room must be separated from the generator by a firewall when the door must be closed. open on the firewall, a class A fire door must be installed.