Hello dear, I am very happy to answer your question. The HF-400GF diesel generator model is installed in parallel with two 300mm2 copper core cables of the same specification for each phase. The neutral line uses a 300MM2 and grounding. The wire uses 300mm2 single-core copper core cable can be installed. When selecting diesel generator cable, ensure that its load capacity (related to cross section) is not less than the safe load current to carry. The current carrying capacity of the cable depends on: (1) The material of the conductor - copper or aluminum (2) Insulating material (3) Characteristics of the protective layer - intermediate layer, armor or shielding (4) Ambient temperature (5 ) Installation method - The selection and installation of low voltage lines exposed, placed in trunking, buried or mixed with other lines must comply with the IEE or regulationsn local. For digital connections, standard cables must be used. (Please refer to relevant local regulations): (1) For distances less than 305 meters (1,000) feet, use number 20 multi-conductor stranded copper wire. (2) Above 305 meters and below 610 meters (2,000) feet, use number 18 multi-conductor stranded copper wire.
How many square meters of cable does the Model HF-400GF Diesel Generator use?
Introduction How many square meters of cable does the HF-400GF diesel generator model use? Hello dear, I am happy to answer your question. The HF-400GF diesel generator model uses 2 cables per phase.