1. The installation site must be well ventilated. There should be sufficient air inlets on the generator side and good air outlets on the diesel engine side. The air outlet area should be more than 1.5 times larger than the water tank area.
2. The area around the installation site should be kept clean, and objects that may generate corrosive gases and vapors such as acids and alkalis should be avoided nearby. Fire extinguishing devices should be equipped wherever possible.
3. If used indoors, the smoke exhaust pipe must be connected outside. The diameter of the pipe must be ≥ the diameter of the silencer smoke outlet pipe. The connected pipe should not have more. more than 3 elbows to ensure that the smoke discharge should be smooth and the pipe should be inclined downward 5-10 degrees to avoid rainwater injection; if thehe drain pipe is installed vertically upwards, a rain cover must be installed.
4. Basic Use When installing concrete, a level ruler should be used to measure flatness during installation to ensure the unit is secured to a level foundation. There must be special anti-vibration pads or anchor bolts between the unit and the foundation.
5. The unit shell must have reliable protective grounding. For generators that require a neutral point to be directly grounded, the neutral point must be professionally grounded and equipped with lightning protection devices. use commercial electric generators. The electrical grounding device leads the neutral point to be directly grounded.
6. The two-way switch between generator and mains must be very reliable to prevent transreverse power mission. The reliability of the two-way switch wiring must be inspected and approved by the local power supply department.
7. The starting battery wiring must be firm.
First of all, when the Yanan generator is used indoors, the smoke exhaust pipe must be led outside. The diameter of the pipe must be the diameter of the smoke outlet pipe of the silencer. in the pipe should not exceed 3. To ensure smooth flow of smoke exhaust, the pipe should be inclined downward by 5 to 10 degrees to avoid rainwater injection. If the exhaust pipe is installed vertically upwards, a rain cover must be installed. In order to improve the power output of the diesel generator set, when the displacement and number are certain, only by forcing more air into the cylinder to completely burn the fuel in the cylinder canthe average effective pressure of the unit can currently be increased. , diesel generators use turbochargers. The pressure regulator has strict requirements on the exhaust of the diesel generator set. Once the exhaust is not smooth or the exhaust gas velocity does not meet the requirements, the air entering the cylinder will be reduced, causing it to be reduced. cause a reduction in the load capacity of the diesel generator set.
Secondly, the area around the Yanan generator should be kept clean, and objects that may produce acidic, alkali and other corrosive gases and steam should be avoided nearby. Fire extinguishing devices should be equipped wherever possible.
Third, the installation site should be well ventilated. There should be enough air inlets on the Yanan generator side and good air outlets on the diesel generator side. Thereair outlet area should be more than 1.5 times larger than the water tank area; the air inlet is not smooth or does not meet the requirements, and less air enters the cylinder, which will cause insufficient fuel in the cylinder and produce carbon deposits. and affect the load capacity of the diesel generator set. Similarly, if the exhaust pipe does not meet the requirements and the oxygen content of the air in the engine room is reduced, it will also cause insufficient fuel in the cylinder and produce carbon deposits. , and affect the load capacity of the diesel generator set.
Fourth, when the foundation is concrete, during installationThe flatness should be measured with a level ruler to ensure that the unit is fixed on a level foundation. There must be special anti-vibration pads or anchor bolts between the unit and the foundation.
FiveSecondly, the unit shell must have reliable protective earthing. For generators that must have a directly grounded neutral point, the neutral grounding must be done by professionals and equipped with lightning protection devices. for commercial use The electrical grounding device leads the neutral point to be directly grounded.
Sixth, the two-way switch between the generator and the mains must be very reliable to prevent power transmission. The reliability of the two-way switch wiring should be inspected and confirmed by the local power supply department.
What materials are needed for installation in the generator room?
The heat dissipation outlet of the water tank adopts an electric blind which is linked with the unit. It only takes 2 seconds to open it 90 degrees, the water tank is equipped with a capot air guide to avoid any problems. the heat does not spread and is directly evacuated outside the computer room; the foundation wall is covered with sound-absorbing and flame-retardant cotton to absorb the sound wave frequency of the unit and reduce noise; The interior wall uses perforated aluminum panels for exterior decoration, which not only achieves a beautiful appearance, but also achieves a sound absorption effect. The muffler is installed on the roof of the engine room
I come from Jiangsu Yuchai Generator Company, do you think this answer can help you?
The situation is different depending on the power of the unit;
The general situation is to transport, hoist and set up first;
Then prepare the materials, bellows, elbows, smoke pipes, large units must be manufactured; Transition oil tank inlet and return pipelines, popositioned and installed according to site conditions. Check the battery fluid, engine oil, and coolant, and be satisfied if not necessary;
Others are mainly: noise reduction and environmental protection projects in the engine room (two types); p>
Installation is important, I can only give you an outline, but I can't explain everything in a few words.