A 250 kW generator is required. bajunsheng's answer is incorrect. A 110 kW pump, even if calculated based on 3 times the rated current, requires a generator of more than 250 kW to start, and it must be a generator from a conventional manufacturer. , otherwise a generator of at least 300 kW is required.
The Ivanfu generator has the greatest ability to start the engine
It cannot drive.
In general, the starting current of a motor is approximately 3 to 5 times the rated current. A single 90 kW motor requires 270 kW to start. However, such a large motor is usually equipped with a soft start, which is the case. less than 3 times. Can start. However, when some motors are equipped with a pump, it is under pressure and the starting current is greater.
A 100 KW generator cannot actually produce 100 KW of power. The power coefficient written on the pThe generator's nameplate is 0.8, or the number 100*0.8. Actual power may vary depending on machine operation, altitude and other factors. 80KW is also inaccessible.
If forced started, the generator will be overloaded, the diesel engine will emit black smoke until it stalls and the equipment may be damaged.
If several motors total 90 kW, forget that first, count the largest, then the second, and so on.