1. Several common faults caused by the generator not producing electricity
(1) Residual magnetism is often lost after shutdown, because the material used for the excitation poles is close to the mild steel. and the residual magnetism is low. The magnetic field disappears when there is no current in the field winding.
(2) The magnetic poles of the generator lose their magnetism.
(3) The field circuit components are damaged or the circuit is open, shorted or grounded.
(4) There is poor contact between the exciter brush and the commutator or insufficient pressure on the brush holder.
(5) The field winding is incorrectly wired and has opposite polarity.
(6) The generator brush and slip ring have poor contact or the brush pressure is insufficient.
(7) Generator stator winding or rotor winding is open circuitt.
(8) Generator lead wire wiring is loose or switch has poor contact.
(9) The fuse is blown
2. Common troubleshooting methods when generator fails to generate electricity
(1) The backup battery must be magnetized before generating electricity.
(2) A direct current greater than the rated current (for a short period) is transmitted into the winding for magnetization. The specific current is determined by the test.
(3) Replace damaged components and repair faulty lines.
(4) Remove sharp dirt on the contact surface, adjust the brush pressure and tighten the brush holder.
(5) Correct the wiring and press the correct polarity for magnetization.
(6) Remove the sharp scales on the contact surface, grind the brush, and adjust the brush pressure so that the brush and the slip ring are in close contact.
(7) Check and repair the broken circuit.
(8) Connect the connector or repair the contact part of the switch.
(9) After identifying the cause of the fuse and concluding that the generator itself and the circuit are normal, replace the specified fuse.
In fact, to prevent this kind of problem from happening, you should always be careful that there are major problems with the generator. It is best to carry out regular maintenance.
Connect the starter and distinguish the positive and negative poles of the motor and the positive and negative poles of the battery. This is the positive pole and the one at the end is the negative pole. must be connected in series directly to obtain the effect of 24 volts. Connect the positive pole of the motor first, do not let the terminal touch other terminals. Then connect the negative pole of the motor. be connected safely to avoid sparking and burning the terminal.
Reference documents:
www.ouyi168.com