The mobile power station of the civil air defense is a diesel generator room. The mobile power station is composed of a generator room, an oil storage room, an air inlet diffusion room, an exhaust diffusion room, a smoke exhaust valve room, an exhaust, The smoke exhaust well does not require the installation of oil wells.
An oil well is a well that is drilled from the ground to the oil layer with a drilling rig when extracting oil. It is a hole drilled through drilling methods.
1. The following points should be noted when locating the computer room: ① When it is set up on the underground floor, try to have one side close to the outer wall to facilitate ventilation and smoke exhaust. ② Keep it as close as possible to the power substation and distribution station to shorten the cable length, wiring and reduce power loss. ③ Pay attention to the convenience of hoisting and maintenance of the unit.
2. The diesel generator room should be separated from other parts by 2.00h fire-resistant partition walls and 1.50h fire-resistant floors according to the fire protection level.
3. An oil storage room should be set up separately, and the oil storage capacity should not exceed the required amount for 8 hours. The oil storage room should be separated from the generator by a firewall, and a fire alarm device and fire extinguishing facilities should be installed.
4. Dry fire-fighting sand is installed inside the computer room.
5. Set up eye-catching icons and text prohibiting fireworks around the computer room.
6. There are fire hydrants, fire hoses and fire water guns outside the computer room.