1. The number of air changes in the oil storage room of the diesel generator room is ≧5 times/h.
2. The number of air changes in the substation room is 5-8 times/h, and the number of air changes in the power distribution room is 3-4 times/h.
3. The number of air changes in the refrigeration machine room is 4-6 times/h.
4. The number of air changes in the fuel oil boiler room and direct fuel fire engine room is ≧ 3 times/h, and the number of air changes in accidental ventilation is ≧ 6 times. /h.
5. The number of air changes in gas boiler rooms and direct-fired gas engine rooms is ≧6 times/h, and the number of air changes in accidental ventilation is ≧12 times/h.
6. The ventilation volume of the oil depot should be ≥6 air changes/h; the ventilation volume of the oil pump room must bebe ≥12 air changes/h when calculating the air changes of both; , the height of the room can generally be 4 m;
7. The ventilation volume between underground daily fuel tanks should be ≥3 hours/h.
8. The gas pressure regulating and metering room should be equipped with a continuous exhaust system and the ventilation volume should be ≥ 3 air changes/h, the accidental ventilation volume should be ≥ 12 air changes 'air/hr; .
9. The laundry room can be estimated based on the following air change times: The air change rate for production rooms is 20 to 30 times/h. Where there are local ventilation installations, the overall extract air rate. is 5 times/h. The ventilation frequency is 2 to 3 times/h; the ventilation frequency of auxiliary rooms is 15 times/h. Living spaces must comply with relevant specifications.
10. LPublic toilets should be ventilated 10 to 15 times/hour; residential bathrooms and boiling water rooms should be ventilated 5 to 10 times/hour; For air-conditioned hotel bathrooms, the exhaust air volume should be based on the fresh air volume in the room 80%~90%.
11. The smokehouse should be equipped with a mechanical exhaust and the exhaust volume should be selected based on 10-15 air changes/h.
12. The elevator machine room can use mechanical ventilation or refrigeration (with its own cold source air conditioner) to cool in summer. The volume of air used for ventilation and cooling can be determined by the air change method. , which is generally 5 to 15 times/h.
13. The ventilation of the darkroom should adopt mechanical exhaust and natural air intake ventilation methods, and the exhaust volume should be ≥5 changemair inlets/h. The air outlet should be located near the pool. The air inlet should use blackout blinds and the wind speed through the blinds should be <2 m/s.
14. The number of air changes in underground storage rooms and bicycle garages is 2 to 4 times/h.
15. Underground garage: Install a mechanical exhaust system. The exhaust system is adjusted according to the fire protection zone. The exhaust volume is 4 times/h (based on a floor height of 3.0 meters). Use low noise fans and no noise reduction measures.
16. The underground equipment room is equipped with a mechanical exhaust system: 5 times/h in the water pump room, 8-10 times/h in the substation and 4 times/h. h in the low electrical machine room