No. The diesel generator room should be installed independently. When installed independently, keep a safe distance from other exhaust pipes. Therefore, the exhaust duct of the diesel generator room cannot pass through the exhaust duct. Diesel generator is a kind of small power generation equipment, which refers to the electric machines which use diesel as fuel and diesel engine as the main engine to drive the generator to produce electricity.
1. The location of the equipment must have good ventilation. There should be sufficient air inlets on the generator side and air outlets on the diesel engine side. The air outlet area should be more than 1.5 times larger than the water tank area (for reference only: (Fujian Yanan diesel generator) Yaxiaonan will answer for you)
2 . be kept propre to avoid placing near objects that may generate corrosive gases and vapors such as acids and alkalis. Fire-fighting equipment should be equipped if possible;
3. When used indoors, the smoke exhaust pipe must be directed outside. The diameter of the pipe must be ≥ the diameter of the smoke outlet pipe. the silent. The diameter of the connected pipe should be There should be no more than 3 bends to ensure smooth flow of smoke exhaust, and the pipe should be inclined downward 5-10 degrees to prevent rainwater to penetrate if the exhaust pipe is installed; vertically upwards, it is necessary to install a rain cover; p>
4. When concrete is used as a foundation, a level ruler should be used to measure its level during installation to ensure the unit is secured to a support. level foundation. Hemust have special anti-vibration pads or anchor bolts between the unit and the foundation;
5. The unit shell must have reliable protective grounding. For generators that require a neutral point to be directly grounded, this is the case. The necessary professionals must carry out the neutral grounding and be equipped with lightning protection equipment. It is strictly prohibited to use mains grounding equipment to directly ground the neutral point;
6. the mains must be very reliable to prevent power transmission. The reliability of the two-way switch wiring must be inspected and certified by the local power supply department.