Yes. 6500W generator can be used at the same time: two 1.5P air conditioners; a 60W TV; an 80W refrigerator; two 5OW fans; a 1500W rice cooker and other household appliances. the equipment will be less than or shortly equal to 6500W. A water heater refers to a device that uses various physical principles to increase the temperature of cold water and turn it into hot water within a certain period of time.
What size generator is needed for a 5 HP three phase refrigeration unit? How to calculate?
The power of a 5 horsepower cooling machine is about 5 kW;
The air conditioner is an "electric appliance" and its starting current is much higher than the running current;
< p> The selected generator must be 10 kVA and above. What size refrigerator is needed for a 240 cubic meter cold room?Depending on the temperaturere, it is more reasonable to use 2 units of 15 HP at around minus 20 degrees and 2 units of 8 HP for cold storage. For rapid freezing in compartments, two 20 horsepower machines are used, one for rapid freezing and one for refrigeration. . . . . . .
How much refrigeration unit is required to reduce 5 cubic meters of water from 25°C to 5°C in one hour?The cooling capacity required to reduce 5 cubic meters of water from 25°C to 5°C is 5*(25-5)*1.163 = 116 kW.
Since the chiller operates more efficiently when the water temperature is high and less efficient when the water temperature is low, it is necessary to reduce the temperature of 5 cubic meters of water by 25 °C to 5°. C in 1 hour. The rated cooling capacity of the required chiller is approximately 116*0.7 = 80 kW, which corresponds to a 32 horsepower unit.
How many refrigerators are needed to builda 120 cubic meter cold room? Do you need to know the temperature of your cold room? Storage type. Quantity in store, etc.
It is recommended to first choose the manufacturer of the refrigeration machine and let them do the calculation.
I hope you can adopt it.
How big a refrigerator is needed for a cold room of 2.7 meters long, 1.9 meters wide and 2.3 meters high.Cold room price need to know cold room construction dimensions details? , calculate and design the quantity of materials used in construction, then calculate the cost. Find a professional manufacturer to customize a suitable solution. If necessary, you can consult Runshuang Refrigeration
How big is a refrigerator for a 200. cubic meter cold storage15P - sufficient
380V - —Required
p>What type of warehouse frigorific is it? What is the temperature of the cold storage? To configure the unit, you need to know the specific conditions of the cold storage - Magsheng Refrigeration
Can be added
Hope to adopt it
2,400 tons water should be reduced from 15 degrees to 7 degrees. How many refrigeration unitsThere is also a question of duration. The longer the cooling time allowed, the fewer refrigeration units needed. conversely, the greater the number of refrigeration units required.
For example, if it is necessary to reduce 2,400 tons of water from 15 degrees to 7 degrees in 4 hours, the required refrigeration capacity of the refrigeration unit is 5,582 kW (2232 horsepower, 1590 tons refrigeration).
Which brand of compressor is used for cold room refrigeration unitThe cold room unit used by our company is Kaideli, la? the compressor is Hanzhong, special cold storage. They are used by Bitzer, Copeland, Dolin, Meiyoule, Refcon and Fujiho. They can be used by general customers with whatever they order.
How much refrigeration unit is needed to cool 1 cubic meter of water from 25 degrees to 12 degrees in 8 hours?The weight of 1 cubic meter of water is m=1000 kg< /p>
The specific heat of water is C=4.18 kg/kg℃< /p>
Temperature difference t=25-12=13℃
Quantity of water heat Q=cmt=4.18X1000X13=54340KJ
1kw=3600kJ/h
Consider the heat dissipation of 1kw
The total load Q1=15kw+1kw=16kw
Now if we want to reduce the water from 25 degree to 12 degree Celsius in 8 hours, the refrigeration unit needs load Q2 = 16/8 = 2 kW
The evaporation temperature is 5 ℃, and the condenser adopts an air-cooled form. and the condensation temperature is45℃, then the unit should choose 3 horsepower semi-enclosed air-cooled condensing unit. Yes, it can provide approximately 3 kW/h cooling capacity under these operating conditions to meet your needs.
In addition, it is best to stir 1 cubic meter of water for better heat exchange.