Are there any 100 kilowatt aluminum generators in 2002? According to the China Science Popularization Network, common structural materials for 100-kilowatt generators in 2002 include iron, copper, steel, etc. Although aluminum is also a common metal material, it was not generally used as the primary construction material in generators of the time. For generators, copper is typically used for electrical components such as wires, coils and windings, while iron and steel are used for mechanical structures and magnetic circuit components. These metals are more widely used in generators. In 2002, aluminum could have been used in other applications, such as generator housings or other non-critical components, but it was unlikely to be used as a primary construction material.
A generatorof 100 kilowatts can drive a 90 kilowatt underground pump
According to your question, Shanghai Yizhong power plant engineer has a 100 kilowatt generator with a 50 kilowatt load connected . . Where did the remaining 50 kilowatts of energy go? According to the analysis, there are two possibilities. The first is that the 100 kilowatt generator you buy now has less than 100 kilowatts of real power. a backup of 100 kilowatts. It depends on the model and price you buy. If one is 50,000 and the other is 40,000, then the power of 50,000 must be more than 40,000. Therefore, when buying a generator, you should look at the model, not the price. Another possibility is that the load you are connecting is greater than 40,000.50 kilowatts.
It cannot be driven.
In general, the starting current of a motor is approximately 3 to 5 times the rated current. Only one90 kW motor requires 270 kW to start. However, such a large motor is usually equipped with a soft start, which it does. less than 3 times. Can start. However, when some motors are equipped with a pump, it is under pressure and the starting current is greater.
A 100 KW generator cannot actually produce 100 KW of power. The power coefficient listed on the generator nameplate is 0.8, or the number 100*0.8. Actual power may vary depending on machine operation, altitude and other factors. 80KW is also inaccessible.
If forced started, the generator will be overloaded, the diesel engine will emit black smoke until it stalls and the equipment may be damaged.
If several motors total 90 kW, forget that first, count the largest, then the second, and so on.