Main maintenance content (due to the differences in performance and use conditions of different generator sets, the standards listed are for reference only and should be used according to specific conditions)
Routine maintenance:
1. Check whether the connecting bolts of each rotating part are loose and tighten them in time; 2. Check the oil level in the oil pan. If it is insufficient, add oil. Fuel tank ; 4. Check the water surface of the water tank; 5. Check the oil and water pipe joints; 6. Check the inlet and exhaust pipe joints and cylinder seals; remove oil stains and surface dust; clean room;
First level technical maintenance: (50-80 hours) in daily maintenance Added above
1. Clean the air filter and replace it if necessary;
2. Replace the filterdiesel engine, air filter and water filter;
3. Check drive belt tension;
4. Add lubricating oil to all oil nozzles. and lubricating parts;
5. Replace cooling water
Second level technical maintenance: (250-300 hours) added to the contents of daily maintenance and first level maintenance
1. Clean the piston, piston pin, cylinder liner, piston ring, connecting rod bearing and check for wear;
2. Check whether the inner and outer races of the main bearing. are cowardly;
3. Remove scale and sediment in the water channels of the cooling water system;
4. Remove carbon deposits in the cylinder combustion chamber and in the intake passages and d 'exhaust ;
5. Check valves, valve seats, push rods and rocker arms for wear and performgrinding settings.
< p>6. Clean carbon deposits from the turbocharger rotor; wear of bearings and wheels, and replace them if necessary;7. Check whether the bolts on the coupling between the generator and diesel engine are loose or slipping. Problems detected must be repaired.
Third level technical maintenance: (500-1000 hours) added to the contents of daily maintenance, first level maintenance and second level maintenance
1. Check and adjust it. injection angle;
2. Clean the fuel tank;
3. Clean the oil pan
4. p>
My name is Wu 13751169761, sales engineer of Shenzhen Fidiankang Diesel Generator Company. This water tank does not need to be changed after a single use. It can be replaced after a certain period of operation, for example around February. As long as there is water in the water tank pend operation and the machine is not fried, everything will be fine. If it is a generator, it can run continuously because it has many generators that can produce electricity in turn. If it is a single machine, it should run for a while and let the machine rest and cool down. To avoid burning the cylinder and piston! !