I don't know what type of unit you have, but this is generally the phenomenon and treatment
Phenomena: 1. The exhaust gas temperature rises and the vacuum drops sharply . In severe cases, the explosion-proof membrane is broken
2. The increase in the temperature of the circulating water inlet and outlet increases
3 The current of the circulation pump decreases or trembles<. /p>
Process: 1. Quickly reduce the temperature according to the vacuum conditions Load
2 Quickly start the emergency circulation pump
3 Wait for the pump to emergency starts normally and then stops the pump in original operation 2 Y' I# |8 g: ^) C% `8 ?- g
4 Find the cause If it is a circulation pump failure, ask the electrician to intervene quickly. find the cause, repair it as soon as possible and put it on standby&cannot be restored quickly, the portal will stop once the vacuum drops to the specified value. 1 person rated it