The rated power factor of the hydrogenerator shall be:
a) For those with a rated capacity of 100 MVA and below, not less than 0.85 (offset);
b) Rated capacity If the rated capacity is more than 100 MVA but not more than 250 MVA, it should not be less than 0.875 (lag
c) If the rated capacity is more than 250 MVA but not greater than 650 MVA, it must not be less than 0.9 (lag);
d) If the rated capacity is more than 650 MVA, it should not be less than 0.925 (lag).
Note: If the user has special requirements, they can be stipulated in the particular technical agreement.
1. 300 W is the output power of the generator. Power output has nothing to do with the size of the water flow and the output voltage of the generator.
2. The rated output voltage of the generator is related to the design. Its concept is as follows: the nominal voltage valueale which can be emitted at the nominal speed. For example: for a 220 V generator, the rated output voltage should be 220 V; for 380V generator, the rated output voltage should be 380V and for 36V generator, the rated output voltage should be 36V;